| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Air layer between Dabs Concrete block Dense inner leaf Xtratherm XT/CW T&G Cavity unventilated Low E Clay brickwork outer leaf External surface resistance |
- 13 15 100 80 50 105 - |
- 0.180 - 1.150 0.023 - 0.770 - |
0.130 0.069 0.100 0.087 3.478 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
4.732 / 4.698 W/m2 K 0.000 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.43 Plaster 20 0.2 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Air layer between Dabs Concrete block - AERATED Xtratherm XT/CWP (Cavity Plus) T&G Cavity unventilated Low E Clay brickwork outer leaf External surface resistance |
- 13 15 100 60 50 105 - |
- 0.180 - 0.110 0.021 - 0.770 - |
0.130 0.069 0.100 0.583 2.857 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
4.858 / 4.573 W/m2 K 0.000 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.43 Plaster 20 0.2 Not applicable Not applicable |
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.88 Mortar - protected 100 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Xtratherm XT/TL Air layer between Dabs Concrete block Dense inner leaf Xtratherm XT/CW T&G Cavity unventilated Low E Clay brickwork outer leaf External surface resistance |
- 13 38 15 100 60 50 105 - |
- 0.180 0.023 - 1.150 0.023 - 0.770 - |
0.130 0.069 1.652 0.100 0.087 2.609 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
5.515/ 5.481 W/m2 K 0.000 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.43 Plaster 20 0.2 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Air layer between Dabs Concrete block - Aerated Xtratherm XT/CWP (Cavity Plus) T&G Cavity unventilated Low E Clay brickwork outer leaf External surface resistance |
- 13 15 100 75 50 105 - |
- 0.180 - 0.110 0.021 - 0.770 - |
0.130 0.069 0.100 0.583 3.571 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
5.574 / 5.287 W/m2 K 0.000 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.43 Plaster 20 0.2 Not applicable Not applicable |
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.88 Mortar - protected 100 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Xtratherm XT/TL Air layer between Dabs Concrete block Dense inner leaf Xtratherm XT/CW T&G Cavity unventilated Low E Clay brickwork outer leaf External surface resistance |
- 13 50 15 100 75 50 105 - |
- 0.180 0.023 - 1.150 0.023 - 0.770 - |
0.130 0.069 2.174 0.100 0.087 3.261 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
6.689 / 6.655 W/m2 K 0.000 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.43 Plaster 20 0.2 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Xtratherm XT/TL Air layer between Dabs Concrete block Dense inner leaf Xtratherm XT/CWP (Cavity Plus) T&G Cavity unventilated Low E Clay brickwork outer leaf External surface resistance |
- 13 25 15 100 75 50 105 - |
- 0.180 0.023 - 0.110 0.021 - 0.770 - |
0.130 0.069 1.087 0.100 0.583 3.571 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
6.663 / 6.374 W/m2 K 0.000 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.43 Plaster 20 0.2 Not applicable Not applicable |
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.88 Mortar - protected 100 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Xtratherm XT/TF Liner Vapour Control layer Fibreglass between studs Plywood sheathing Breathable membrane Cavity unventilated Brick outer leaf External surface resistance |
- 13 25 0 140 12 0 50 105 - |
- 0.180 0.023 1.000 0.035 0.130 - - 0.770 - |
0.130 0.069 0.870 0.000 2.932 0.092 0.001 0.180 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
4.672 / 4.427 W/m2 K 0.004 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.12 studs 140 0.15 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Vapour Control layer Mineral Fibre between Studs Plywood sheathing Xtratherm XT/SB Cavity unventilated - Low E Brick outer leaf External surface resistance |
- 13 0 140 12 25 50 105 - |
- 0.180 1.000 0.040 0.130 0.023 - 0.770 - |
0.130 0.069 0.000 2.692 0.092 1.087 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
5.169 / 4.897 W/m2 K 0.003 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.12 studs 140 0.15 Air gaps present but no air circulation Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Vapour Control layer Xtratherm XT/TL Mineral Fibre between Studs Plywood sheathing Cavity unventilated Brick outer leaf External surface resistance |
- 13 0 50 140 12 50 105 - |
- 0.180 1.000 0.023 0.040 0.130 - 0.770 - |
0.130 0.069 0.000 2.174 2.692 0.092 0.180 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
5.812 / 5.514 W/m2 K 0.002 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.12 studs 140 0.15 Air gaps present but no air circulation Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Vapour Control layer Mineral Fibre between Studs Plywood sheathing Xtratherm XT/SB Cavity unventilated - Low E Brick outer leaf External surface resistance |
- 13 0 140 12 40 50 105 - |
- 0.180 1.000 0.040 0.130 0.023 - 0.770 - |
0.130 0.069 0.000 2.692 0.092 1.739 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
5.849 / 5.550 W/m2 K 0.002 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.12 studs 140 0.15 Air gaps present but no air circulation Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Vapour Control layer Xtratherm XT/TL Mineral Fibre between Studs Plywood sheathing Cavity unventilated Brick outer leaf External surface resistance |
- 13 0 70 140 12 50 105 - |
- 0.180 1.000 0.023 0.035 0.130 - 0.770 - |
0.130 0.069 0.000 3.043 2.932 0.092 0.180 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
7.073 / 6.624 W/m2 K 0.002 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.12 studs 140 0.15 Air gaps present but no air circulation Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
| Internal surface resistance Plasterboard Vapour Control layer Mineral Fibre between Studs Plywood sheathing Xtratherm XT/SB Cavity unventilated - Low E Brick outer leaf External surface resistance |
- 13 0 140 12 60 50 105 - |
- 0.180 1.000 0.035 0.130 0.023 - 0.770 - |
0.130 0.069 0.000 2.932 0.092 2.609 0.650 0.136 0.040 |
| Upper/lower resistance: Correction for air gaps/mechanical fasteners: |
7.109 / 6.659 W/m2 K 0.002 W/m2 K |
||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.12 studs 140 0.15 Air gaps present but no air circulation Not applicable |
| Floor Perimeter/Area | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
| Required Thickness [mm] | ≥100 | ≥110 | ≥120 | ≥120 | ≥120 | ≥125 | ≥125 |
| Available Thicknesses [mm] | 25, 30, 35, 40, 45, 50, 60, 70, 75, 80, 90, 100, 125, 150 | ||||||
| Floor Perimeter/Area | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
| Required Thickness [mm] | ≥120 | ≥130 | ≥140 | ≥140 | ≥150 | ≥150 | ≥150 |
| Available Thicknesses [mm] | 25, 30, 35, 40, 45, 50, 60, 70, 75, 80, 90, 100, 125, 150 | ||||||
| Floor Perimeter/Area | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
| Required Thickness [mm] | ≥170 | ≥180 | ≥190 | ≥200 | ≥210 | ≥210 | ≥210 |
| Available Thicknesses [mm] | 25, 30, 35, 40, 45, 50, 60, 70, 75, 80, 90, 100, 125, 150 | ||||||
| Floor Perimeter/Area | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
| Required Thickness [mm] | ≥110 | ≥115 | ≥115 | ≥120 | ≥120 | ≥125 | ≥125 |
| Available Thicknesses [mm] | 25, 30, 35, 40, 45, 50, 60, 70, 75, 80, 90, 100, 125, 150 | ||||||
| Floor Perimeter/Area | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
| Required Thickness [mm] | ≥130 | ≥135 | ≥140 | ≥140 | ≥145 | ≥145 | ≥145 |
| Available Thicknesses [mm] | 25, 30, 35, 40, 45, 50, 60, 70, 75, 80, 90, 100, 125, 150 | ||||||
| Floor Perimeter/Area | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
| Required Thickness [mm] | ≥180 | ≥185 | ≥190 | ≥190 | ≥195 | ≥195 | ≥195 |
| Available Thicknesses [mm] | 25, 30, 35, 40, 45, 50, 60, 70, 75, 80, 90, 100, 125, 150 | ||||||
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
||
| Outer Resistance Tile/Batten Space Breather Membrane Unvented Void below Breather min 25mm Xtratherm XT/PR between rafters 600cs Xtratherm XT/TL below rafters Vapour Control layer Plasterboard Internal surface resistance |
- 1 1 25 30 125 0 13 - |
- 1.000 1.000 0.023 - 0.023 1.000 0.180 - |
0.100 0.001 0.001 0.532 1.304 3.921 0.000 0.069 0.100 |
||
|
|||||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Timber Joists 125 0.083 Air gaps present but no air circulation Not applicable |
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Softwood 25 0.083 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
||
| Outer Resistance Tile/Batten Space Breather Membrane Xtratherm XT/SK T&G over rafters Xtratherm XT/PR between rafters 600cs Air layer, upward heat flow, emissivities 0.05 / 0.9 Vapour Control layer Plasterboard Internal surface resistance |
- 1 1 80 100 25 0 13 - |
- 1.000 1.000 0.023 0.023 - 1.000 0.180 - |
0.100 0.001 0.001 3.478 3.169 0.320 0.000 0.069 0.100 |
||
|
|||||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Timber Joists 100 0.08 Air gaps present but no air circulation Not applicable |
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Softwood 25 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
||
| Outer Resistance Tile/Batten Space Breather Membrane Xtratherm XT/SK T&G over rafters Xtratherm XT/PR between rafters 600cs Air layer, upward heat flow, emissivities 0.05 / 0.9 Vapour Control layer Plasterboard Internal surface resistance |
- 1 1 100 150 25 0 13 - |
- 1.000 1.000 0.023 0.023 - 1.000 0.180 - |
0.100 0.001 0.001 4.348 4.753 0.320 0.000 0.069 0.100 |
||
|
|||||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Timber Joists 150 0.08 Air gaps present but no air circulation Not applicable |
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Softwood 25 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
||
| External surface resistance Roof space Mineral wool quilt between joists 600cs Xtratherm XT/TL under joists Plasterboard Internal surface resistance |
- - 200 40 13 - |
- - 0.040 0.023 0.180 - |
0.040 0.200 3.910 1.739 0.069 0.100 |
||
|
|||||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Timber Joists 150 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
||
| External surface resistance Roof space Mineral wool quilt over joists Mineral wool quilt between joists 600cs Xtratherm XT/TL under joists Plasterboard Internal surface resistance |
- - 100 150 40 13 - |
- - 0.040 0.040 0.023 0.180 - |
0.040 0.200 3.500 3.178 1.739 0.069 0.100 |
||
|
|||||
| Is there repeating
thermal bridging? Bridging conductivity [W/m K] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Timber Joists 150 0.08 Not applicable Not applicable |
| Layers | Thickness [mm] |
Conductivity [W/m2 K] |
Resistance [m2 K/W] |
||
| External surface resistance Roof space Mineral wool quilt over joists Mineral wool quilt between joists 600cs Xtratherm XT/TL under joists Plasterboard Internal surface resistance |
- - 150 150 60 13 - |
- - 0.040 0.040 0.023 0.180 - |
0.040 0.200 3.750 3.178 2.609 0.069 0.100 |
||
|
|||||
| Is there repeating
thermal bridging? Bridging conductivity [W/mK] Bridging material Bridging thickness [mm] Fractional area of bridging [-] Correction for air gaps Correction for mechanical fasteners |
Yes 0.13 Timber Joists 150 0.08 Not applicable Not applicable |